- #!/bin/sh /etc/rc.common
-
- START=60
- USE_PROCD=1
- UPSMON_C=/var/etc/nut/upsmon.conf
-
- nut_upsmon_conf() {
- local cfg="$1"
-
- echo "# Config file automatically generated from UCI config" > $UPSMON_C
-
- config_get runas "$cfg" runas "nut"
- [ -n "$runas" ] && echo "RUN_AS_USER $runas" >> $UPSMON_C
-
- config_get val "$cfg" minsupplies 1
- echo "MINSUPPLIES $val" >> $UPSMON_C
-
- config_get val "$cfg" shutdowncmd "/sbin/halt"
- echo "SHUTDOWNCMD \"$val\"" >> $UPSMON_C
-
- config_get val "$cfg" notifycmd
- [ -n "$val" ] && echo "NOTIFYCMD \"$val\"" >> $UPSMON_C
-
- config_get val "$cfg" pollfreq 5
- echo "POLLFREQ $val" >> $UPSMON_C
-
- config_get val "$cfg" pollfreqalert 5
- echo "POLLFREQALERT $val" >> $UPSMON_C
-
- config_get val "$cfg" hostsync 15
- echo "HOSTSYNC $val" >> $UPSMON_C
-
- config_get val "$cfg" deadtime 15
- echo "DEADTIME $val" >> $UPSMON_C
-
- config_get val "$cfg" powerdownflag /var/run/killpower
- echo "POWERDOWNFLAG $val" >> $UPSMON_C
-
- config_get val "$cfg" onlinemsg
- [ -n "$val" ] && echo "NOTIFYMSG ONLINE \"$val\"" >> $UPSMON_C
- config_get val "$cfg" onbattmsg
- [ -n "$val" ] && echo "NOTIFYMSG ONBATT \"$val\"" >> $UPSMON_C
- config_get val "$cfg" lowbattmsg
- [ -n "$val" ] && echo "NOTIFYMSG LOWBATT \"$val\"" >> $UPSMON_C
- config_get val "$cfg" fsdmsg
- [ -n "$val" ] && echo "NOTIFYMSG FSD \"$val\"" >> $UPSMON_C
- config_get val "$cfg" commokmsg
- [ -n "$val" ] && echo "NOTIFYMSG COMMOK \"$val\"" >> $UPSMON_C
- config_get val "$cfg" commbadmsg
- [ -n "$val" ] && echo "NOTIFYMSG COMMBAD \"$val\"" >> $UPSMON_C
- config_get val "$cfg" shutdownmsg
- [ -n "$val" ] && echo "NOTIFYMSG SHUTDOWN \"$val\"" >> $UPSMON_C
- config_get val "$cfg" replbattmsg
- [ -n "$val" ] && echo "NOTIFYMSG REPLBATT \"$val\"" >> $UPSMON_C
- config_get val "$cfg" nocommmsg
- [ -n "$val" ] && echo "NOTIFYMSG NOCOMM \"$val\"" >> $UPSMON_C
- config_get val "$cfg" noparentmsg
- [ -n "$val" ] && echo "NOTIFYMSG NOPARENT \"$val\"" >> $UPSMON_C
-
- notifylist() {
- local value="$1"
- append optval "$value" "+"
- }
-
- setnotify() {
- local cfg="$1"
- local optname="$2"
- local optval
- config_list_foreach "$cfg" "$optname" notifylist
- if [ -z "$optval" ]; then
- # If no list fallback to trying option, fallback to default
- config_get optval "$cfg" "$optname" "$default"
- if [ -n "$optval" ]; then
- echo "$optval"
- else
- # No default, so do the NUT default
- echo "SYSLOG"
- fi
- else
- echo "$optval"
- fi
- }
-
- local default optval
- val=""
- config_list_foreach "$cfg" defaultnotify notifylist
- default="$optval"
- echo "NOTIFYFLAG ONLINE $(setnotify "$cfg" onlinenotify)" >> $UPSMON_C
- echo "NOTIFYFLAG ONBATT $(setnotify "$cfg" onbattnotify)" >> $UPSMON_C
- echo "NOTIFYFLAG LOWBATT $(setnotify "$cfg" lowbatnotify)" >> $UPSMON_C
- echo "NOTIFYFLAG FSD $(setnotify "$cfg" fsdnotify)" >> $UPSMON_C
- echo "NOTIFYFLAG COMMOK $(setnotify "$cfg" commoknotify)" >> $UPSMON_C
- echo "NOTIFYFLAG COMMBAD $(setnotify "$cfg" commbadnotify)" >> $UPSMON_C
- echo "NOTIFYFLAG SHUTDOWN $(setnotify "$cfg" shutdownnotify)" >> $UPSMON_C
- echo "NOTIFYFLAG REPLBATT $(setnotify "$cfg" repolbattnotify)" >> $UPSMON_C
- echo "NOTIFYFLAG NOCOMM $(setnotify "$cfg" nocommnotify)" >> $UPSMON_C
- echo "NOTIFYFLAG NOPARENT $(setnotify "$cfg" noparentnotify)" >> $UPSMON_C
-
- config_get val "$cfg" rbwarntime 43200
- echo "RBWARNTIME $val" >> $UPSMON_C
-
- config_get val "$cfg" nocommwarntime 300
- echo "NOCOMMWARNTIME $val" >> $UPSMON_C
-
- config_get val "$cfg" finaldelay 5
- echo "FINALDELAY $val" >> $UPSMON_C
-
- config_get val "$cfg" certpath
- if [ -n "$val" ]; then echo "CERTPATH $val" >> $UPSMON_C; fi
-
- config_get_bool val "$cfg" certverify 0
- if [ -n "$val" ]; then echo "CERTVERIFY $val" >> $UPSMON_C; fi
-
- config_get_bool val "$cfg" forcessl 0
- if [ -n "$val" ]; then echo "FORCESSL $val" >> $UPSMON_C; fi
- }
-
- nut_upsmon_add() {
- local cfg="$1"
- local type="$2"
- local upsname
- local hostname
- local port
- local powervalue
- local username
- local password
- local system
-
- # if UPSMON_C is a symlink we're only doing generated config
- [ -L $UPSMON_C ] && {
- rm -f $UPSMON_C
- nut_upsmon_conf ""
- }
-
- config_get upsname "$cfg" upsname
- config_get hostname "$cfg" hostname localhost
- config_get port "$cfg" port
- config_get powervalue "$cfg" powervalue 1
- config_get username "$cfg" username
- config_get password "$cfg" password
- system="$upsname@$hostname"
- if [ -n "$port" ]; then
- system="$system:$port";
- fi
- echo "MONITOR $system $powervalue $username $password $type" >> $UPSMON_C
- }
-
- start_service() {
- mkdir -p "$(dirname "$UPSMON_C")"
- chmod 750 "$(dirname "$UPSMON_C")"
-
- config_load nut_monitor
-
- config_foreach nut_upsmon_conf upsmon
- config_foreach nut_upsmon_add master master
- config_foreach nut_upsmon_add slave slave
-
- [ -z "$(cat /var/etc/nut/nut.conf)" ] && echo "MODE=netclient" >>/var/etc/nut/nut.conf
-
- chmod 640 $UPSMON_C
- chmod 640 /var/etc/nut/nut.conf
-
- chown ${runas:-root}:$(id -gn ${runas:-root}) /var/etc/nut
- chown ${runas:-root}:$(id -gn ${runas:-root}) /var/etc/nut/nut.conf
- chown ${runas:-root}:$(id -gn ${runas:-root}) $UPSMON_C
-
- [ -d /var/run/nut ] || {
- mkdir -m 0750 -p /var/run/nut
- chown ${runas:-root}:$(id -gn ${runas:-root}) /var/run/nut
- }
-
- exec $DEBUG /usr/sbin/upsmon $UPSMON_OPTIONS
- }
-
- stop_service() {
- exec /usr/sbin/upsmon -c stop
- }
-
- reload_service() {
- exec /usr/sbin/upsmon -c reload
- }
|