#!/bin/sh /etc/rc.common START=51 USE_PROCD=1 UPSMON_C=/var/etc/nut/upsmon.conf nut_upsmon_conf() { local cfg="$1" local RUNAS val optval echo "# Config file automatically generated from UCI config" > "$UPSMON_C" config_get RUNAS "$cfg" runas "nutmon" [ -n "$RUNAS" ] && echo "RUN_AS_USER $RUNAS" >> "$UPSMON_C" runas=$RUNAS config_get val "$cfg" minsupplies 1 echo "MINSUPPLIES $val" >> "$UPSMON_C" config_get val "$cfg" shutdowncmd "/usr/sbin/nutshutdown" echo "SHUTDOWNCMD \"$val\"" >> "$UPSMON_C" config_get val "$cfg" notifycmd [ -n "$val" ] && echo "NOTIFYCMD \"$val\"" >> "$UPSMON_C" config_get val "$cfg" pollfreq 5 echo "POLLFREQ $val" >> "$UPSMON_C" config_get val "$cfg" pollfreqalert 5 echo "POLLFREQALERT $val" >> "$UPSMON_C" config_get val "$cfg" hostsync 15 echo "HOSTSYNC $val" >> "$UPSMON_C" config_get val "$cfg" deadtime 15 echo "DEADTIME $val" >> "$UPSMON_C" echo "POWERDOWNFLAG /var/run/killpower" >> "$UPSMON_C" config_get val "$cfg" onlinemsg [ -n "$val" ] && echo "NOTIFYMSG ONLINE \"$val\"" >> "$UPSMON_C" config_get val "$cfg" onbattmsg [ -n "$val" ] && echo "NOTIFYMSG ONBATT \"$val\"" >> "$UPSMON_C" config_get val "$cfg" lowbattmsg [ -n "$val" ] && echo "NOTIFYMSG LOWBATT \"$val\"" >> "$UPSMON_C" config_get val "$cfg" fsdmsg [ -n "$val" ] && echo "NOTIFYMSG FSD \"$val\"" >> "$UPSMON_C" config_get val "$cfg" commokmsg [ -n "$val" ] && echo "NOTIFYMSG COMMOK \"$val\"" >> "$UPSMON_C" config_get val "$cfg" commbadmsg [ -n "$val" ] && echo "NOTIFYMSG COMMBAD \"$val\"" >> "$UPSMON_C" config_get val "$cfg" shutdownmsg [ -n "$val" ] && echo "NOTIFYMSG SHUTDOWN \"$val\"" >> "$UPSMON_C" config_get val "$cfg" replbattmsg [ -n "$val" ] && echo "NOTIFYMSG REPLBATT \"$val\"" >> "$UPSMON_C" config_get val "$cfg" nocommmsg [ -n "$val" ] && echo "NOTIFYMSG NOCOMM \"$val\"" >> "$UPSMON_C" config_get val "$cfg" noparentmsg [ -n "$val" ] && echo "NOTIFYMSG NOPARENT \"$val\"" >> "$UPSMON_C" notifylist() { local value="$1" append optval "$value" "+" } setnotify() { local cfg="$1" local optname="$2" local optval config_list_foreach "$cfg" "$optname" notifylist if [ -z "$optval" ]; then # If no list fallback to trying option, fallback to default config_get optval "$cfg" "$optname" "$default" if [ -n "$optval" ]; then echo "$optval" else # No default, so do the NUT default echo "SYSLOG" fi else echo "$optval" fi } local default optval val="" config_list_foreach "$cfg" defaultnotify notifylist default="$optval" echo "NOTIFYFLAG ONLINE $(setnotify "$cfg" onlinenotify)" >> "$UPSMON_C" echo "NOTIFYFLAG ONBATT $(setnotify "$cfg" onbattnotify)" >> "$UPSMON_C" echo "NOTIFYFLAG LOWBATT $(setnotify "$cfg" lowbatnotify)" >> "$UPSMON_C" echo "NOTIFYFLAG FSD $(setnotify "$cfg" fsdnotify)" >> "$UPSMON_C" echo "NOTIFYFLAG COMMOK $(setnotify "$cfg" commoknotify)" >> "$UPSMON_C" echo "NOTIFYFLAG COMMBAD $(setnotify "$cfg" commbadnotify)" >> "$UPSMON_C" echo "NOTIFYFLAG SHUTDOWN $(setnotify "$cfg" shutdownnotify)" >> "$UPSMON_C" echo "NOTIFYFLAG REPLBATT $(setnotify "$cfg" repolbattnotify)" >> "$UPSMON_C" echo "NOTIFYFLAG NOCOMM $(setnotify "$cfg" nocommnotify)" >> "$UPSMON_C" echo "NOTIFYFLAG NOPARENT $(setnotify "$cfg" noparentnotify)" >> "$UPSMON_C" config_get val "$cfg" rbwarntime 43200 echo "RBWARNTIME $val" >> "$UPSMON_C" config_get val "$cfg" nocommwarntime 300 echo "NOCOMMWARNTIME $val" >> "$UPSMON_C" config_get val "$cfg" finaldelay 5 echo "FINALDELAY $val" >> "$UPSMON_C" config_get val "$cfg" certpath if [ -n "$val" ]; then echo "CERTPATH $val" >> "$UPSMON_C"; fi config_get_bool val "$cfg" certverify 0 if [ -n "$val" ]; then echo "CERTVERIFY $val" >> "$UPSMON_C"; fi config_get_bool val "$cfg" forcessl 0 if [ -n "$val" ]; then echo "FORCESSL $val" >> "$UPSMON_C"; fi havemon=1 } nut_upsmon_add() { local cfg="$1" local type="$2" local upsname local hostname local port local powervalue local username local password local system config_get upsname "$cfg" upsname config_get hostname "$cfg" hostname localhost config_get port "$cfg" port config_get powervalue "$cfg" powervalue 1 config_get username "$cfg" username config_get password "$cfg" password system="$upsname@$hostname" if [ -n "$port" ]; then system="$system:$port"; fi echo "MONITOR $system $powervalue $username $password $type" >> "$UPSMON_C" havems=1 } build_config() { local runas mkdir -m 0750 -p "$(dirname "$UPSMON_C")" config_load nut_monitor config_foreach nut_upsmon_conf upsmon config_foreach nut_upsmon_add master master config_foreach nut_upsmon_add slave slave [ ! -s "$(cat /var/etc/nut/nut.conf)" ] && { echo "MODE=netclient" >>/var/etc/nut/nut.conf chmod 640 /var/etc/nut/nut.conf chgrp $(id -gn ${runas:-root}) /var/etc/nut/nut.conf } [ -s "$UPSMON_C" ] && chmod 640 "$UPSMON_C" [ -s "$UPSMON_C" ] && chgrp $(id -gn ${runas:-root}) "$UPSMON_C" } start_service() { local havemon havems build_config [ "$havemon" != 1 ] && return [ "$havems" != 1 ] && return procd_open_instance "upsmon" procd_set_param respawn procd_set_param stderr 0 procd_set_param stdout 1 procd_set_param command /usr/sbin/upsmon -D procd_close_instance } reload_service() { if pgrep upsmon >/dev/null 2>/dev/null; then build_config /usr/sbin/upsmon -c reload else stop sleep 2 start_service fi } service_triggers() { procd_add_reload_trigger "nut_monitor" }